基于直流电流二倍频分量抑制的电流源型 PWM 整流器控制策略
DOI:
作者:
作者单位:

作者简介:

通讯作者:

中图分类号:

TM46 TH39

基金项目:

重庆市教委科学技术研究重点项目(KJZD-201901102,KJQN202201153)、重庆理工大学研究生创新项目(gzlcx20222020)资助


A localization method of wall-climbing robot based on lidar and improved AMCL
Author:
Affiliation:

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    电流源型脉宽调制整流器在电网电压不平衡工况下运行时,电网电压中负序分量的影响将导致直流侧引起低频脉动, 网侧电流出现低次谐波。 为了解决此问题,在含有源阻尼的传统双闭环控制基础上,利用直流侧电流内环谐振控制直接抑制直 流侧输出低频脉动,同时使网侧电流正弦化;在网侧电流参考指令中加入滤波电容电流补偿项,实现系统网侧电流和电网电压 同相位运行。 为进一步提升系统在高不平衡度工况下运行性能,在调制环节中引入陷波器消除低次谐波分量,提高了网侧电流 波形质量。 最后利用 MATLAB/ Simulink 进行仿真测试,并搭建了一台 3 kW 实验样机,仿真与实验结果表明在电网不平衡度为 6. 7% 和 20% 时,文中所提出控制策略均能将直流侧电压波动限制在 1. 2 V 以内,同时网侧电流总谐波畸变率小于 4% 。

    Abstract:

    When the current source PWM rectifier is at the operate condition that the grid voltage is unbalanced, the negative sequence component of grid voltage will cause low-frequency pulsation in DC side and low-order harmonics in grid side current. To solve this problem, the resonance control with the inner DC current loop based on the traditional double closed loop with active damping is applied in this article to directly suppress low-frequency pulsation existed in the DC side outputs, and the sinusoidal current at the grid side is formed. Besides, the current of the filter capacitor as the compensation term is added into the current reference value on the grid side. In this case, current and voltage with the same phase are realized on the grid side. Furthermore, to improve the operating performance of the system under extremely unbalance conditions, a notch filter is introduced in the modulation link to eliminate low-order harmonic components, which improves the current waveform on grid side. Finally, simulation test is studied by using MATLAB/ Simulink and a 3 kW prototype is established. The simulation and experimental results indicate that when the unbalance degree of the grid reach 6. 7% and 20% , the proposed control strategy can effectively suppress the voltage fluctuation on DC side within 1. 2 V, and the total harmonic distortion rate on the grid side current is less than 4% .

    参考文献
    相似文献
    引证文献
引用本文

黄勇军,郭 强,李海啸.基于直流电流二倍频分量抑制的电流源型 PWM 整流器控制策略[J].仪器仪表学报,2022,43(12):228-237

复制
分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:
  • 最后修改日期:
  • 录用日期:
  • 在线发布日期: 2023-07-04
  • 出版日期: